1449

UnclassifiedGeneral

What This Code Means

Frequency has gone above the Overfrequency Threshold for the duration registered in Overfrequency Delay parameter

Possible Causes

  • •Alternator frequency is 6 hertz above nominal frequency
  • •Alternator line frequency exceeds the Overfrequency Threshold (2 to 10 Hz over) for the duration of the Overfrequency Delay (100 to 2000 half cycles)
  • •Defective Base board
  • •Fault Simulation is Enabled
  • •Fault threshold is not set correctly with PC based service tool
  • •Frequency exceeded Overfrequency Threshold
  • •Fuel or air delivery problem
  • •Genset over frequency for approximately 10 seconds
  • •Loose connector (P22/P18)
  • •Overfrequency Threshold is Set Too Low

Suggested Actions

  1. 1Connect with InPower and ensure that the Fault simulation for Overfrequency Enable is not enabled.
  2. 2Go to Setup > OEM Setup > OEM ALT Setup > Overfrequency Threshold on the operator panel menu and set the Overfrequency Threshold Parameter appropriately for the application.
  3. 3If InPower is not available, cycle power to the control: Depress the Emergency Stop button and wait 30 seconds; disconnect/disable the battery charger; disconnect the battery (disconnect negative first); leave the controller without power for 1 minute; reconnect the battery, enable the battery charger, pullout the E-Stop button, and reset the control (in this order).
  4. 4Refer to the engine service manual
  5. 5Repair connections (P22/P18) or replace the Base board if necessary
  6. 6Reset the threshold to the highest allowable setting after determining the required operating range

ASK RUDY ABOUT THIS FAULT

Get a diagnosis walkthrough for 1449 on your specific Cummins unit — cited to the OEM manual, not a forum guess.

GET THE ANSWER

Free account required — we'll bring your question with you.