1446
UnclassifiedGeneral
What This Code Means
One or more of the phase voltages has exceeded 130% of nominal for 1 seconds; One or more of the phase voltages has exceeded the High AC Voltage Threshold for the High AC Voltage Delay seconds; Engine will shut down
Possible Causes
- •AC voltage exceeding threshold for the duration of the time delay
- •Fault Simulation is Enabled
- •Fault simulation was enabled with a PC based service tool
- •Fault threshold is not set correctly with the PC based service tool
- •High AC voltage fault condition
- •One or more line-to-neutral phase voltages has exceeded 130% of nominal for 0 seconds
- •One or more line-to-neutral phase voltages has exceeded high AC voltage threshold of nominal for time delay seconds
- •Single step large block load removal
- •The Base board or generator is defective
Suggested Actions
- 1Clear the fault and restart the genset
- 2Connect with InPower and ensure that the fault simulation for High AC Voltage is not enabled.
- 3Determine the required operating range before adjusting the threshold
- 4Disconnect the battery (disconnect negative first).
- 5Disconnect/disable the battery charger.
- 6If InPower is not available, cycle power to the control: Depress the Emergency Stop button and wait 30 seconds.
- 7If you do not have a PC based service tool, remove battery power from the control to disable the fault simulation overrides
- 8Reset the threshold to the highest allowable setting
- 9With a PC based service tool, verify that the related fault simulation is not enabled