1446

UnclassifiedGeneral

What This Code Means

One or more of the phase voltages has exceeded 130% of nominal for 1 seconds; One or more of the phase voltages has exceeded the High AC Voltage Threshold for the High AC Voltage Delay seconds; Engine will shut down

Possible Causes

  • •AC voltage exceeding threshold for the duration of the time delay
  • •Fault Simulation is Enabled
  • •Fault simulation was enabled with a PC based service tool
  • •Fault threshold is not set correctly with the PC based service tool
  • •High AC voltage fault condition
  • •One or more line-to-neutral phase voltages has exceeded 130% of nominal for 0 seconds
  • •One or more line-to-neutral phase voltages has exceeded high AC voltage threshold of nominal for time delay seconds
  • •Single step large block load removal
  • •The Base board or generator is defective

Suggested Actions

  1. 1Clear the fault and restart the genset
  2. 2Connect with InPower and ensure that the fault simulation for High AC Voltage is not enabled.
  3. 3Determine the required operating range before adjusting the threshold
  4. 4Disconnect the battery (disconnect negative first).
  5. 5Disconnect/disable the battery charger.
  6. 6If InPower is not available, cycle power to the control: Depress the Emergency Stop button and wait 30 seconds.
  7. 7If you do not have a PC based service tool, remove battery power from the control to disable the fault simulation overrides
  8. 8Reset the threshold to the highest allowable setting
  9. 9With a PC based service tool, verify that the related fault simulation is not enabled