1448
UnclassifiedGeneral
What This Code Means
Frequency dropped below Underfrequency Threshold for the set Underfrequency Delay parameter
Possible Causes
- •Alternator frequency is 6 hertz under nominal frequency
- •Alternator line frequency falls below the Underfrequency Threshold (2 to 10 Hz under) for the duration of the Underfrequency Time Delay (500 to 2000 half cycles)
- •Damaged voltage regulator
- •Defective Base board
- •Faulty rotating rectifier assembly (diodes CR1 through CR6)
- •Genset under frequency for approximately 10 seconds
- •Governor fault
- •Improper connections at generator output terminals
- •Incorrect voltage sense or setup wiring connection
- •Loose connector (P22/P18)
- •Overload
- •The fault threshold is not set correctly with PC based service tool
- •There is a fuel or air delivery problem
- •There is an overload
- •Underfrequency fault condition active for the duration of time delay
Suggested Actions
- 1Bring the generator to idle
- 2Check connections
- 3Check each diode
- 4Check for current spikes
- 5Check for motor starts
- 6Check for overload
- 7Check inrush current
- 8Check operation by disconnecting the load and restarting the generator set
- 9Check operation by disconnecting the load and restarting the unit
- 10Check that load is within proper operating range
- 11Check the fuel shutoff solenoid adjustment
- 12Check the fuel supply
- 13Check the intake air supply
- 14Check the load
- 15Check the load and correct any overload
- 16Compare connections in generator to wiring schematic
- 17Connect InPower
- 18Correct according to the appropriate schematic as needed
- 19Correct any overload
- 20Determine the required operating range before adjusting the threshold
- 21Disconnect the generator control harness from the voltage regulator
- 22Inspect the voltage regulator and the generator control harness connector pins
- 23Refer to the engine service manual
- 24Repair connections (P22/P18) or replace the Base board if necessary
- 25Reset the threshold to the lowest allowable setting
- 26Turn off the generator
- 27Using InPower, verify that the AC voltage output is greater than residual
- 28Verify that excitation inputs J18–1 and J18–2 are connected to the correct generator PMG terminals
- 29Verify that the voltage sensing inputs J22-1, J22-2, J22-3, and J22-4 are connected to L1, L2, L3, and L4 respectively
- 30Visually inspect for corroded pins, bent or broken pins, pushed back or expanded pins