1448

UnclassifiedGeneral

What This Code Means

Frequency dropped below Underfrequency Threshold for the set Underfrequency Delay parameter

Possible Causes

  • •Alternator frequency is 6 hertz under nominal frequency
  • •Alternator line frequency falls below the Underfrequency Threshold (2 to 10 Hz under) for the duration of the Underfrequency Time Delay (500 to 2000 half cycles)
  • •Damaged voltage regulator
  • •Defective Base board
  • •Faulty rotating rectifier assembly (diodes CR1 through CR6)
  • •Genset under frequency for approximately 10 seconds
  • •Governor fault
  • •Improper connections at generator output terminals
  • •Incorrect voltage sense or setup wiring connection
  • •Loose connector (P22/P18)
  • •Overload
  • •The fault threshold is not set correctly with PC based service tool
  • •There is a fuel or air delivery problem
  • •There is an overload
  • •Underfrequency fault condition active for the duration of time delay

Suggested Actions

  1. 1Bring the generator to idle
  2. 2Check connections
  3. 3Check each diode
  4. 4Check for current spikes
  5. 5Check for motor starts
  6. 6Check for overload
  7. 7Check inrush current
  8. 8Check operation by disconnecting the load and restarting the generator set
  9. 9Check operation by disconnecting the load and restarting the unit
  10. 10Check that load is within proper operating range
  11. 11Check the fuel shutoff solenoid adjustment
  12. 12Check the fuel supply
  13. 13Check the intake air supply
  14. 14Check the load
  15. 15Check the load and correct any overload
  16. 16Compare connections in generator to wiring schematic
  17. 17Connect InPower
  18. 18Correct according to the appropriate schematic as needed
  19. 19Correct any overload
  20. 20Determine the required operating range before adjusting the threshold
  21. 21Disconnect the generator control harness from the voltage regulator
  22. 22Inspect the voltage regulator and the generator control harness connector pins
  23. 23Refer to the engine service manual
  24. 24Repair connections (P22/P18) or replace the Base board if necessary
  25. 25Reset the threshold to the lowest allowable setting
  26. 26Turn off the generator
  27. 27Using InPower, verify that the AC voltage output is greater than residual
  28. 28Verify that excitation inputs J18–1 and J18–2 are connected to the correct generator PMG terminals
  29. 29Verify that the voltage sensing inputs J22-1, J22-2, J22-3, and J22-4 are connected to L1, L2, L3, and L4 respectively
  30. 30Visually inspect for corroded pins, bent or broken pins, pushed back or expanded pins