1447
UnclassifiedGeneral
What This Code Means
Engine will shut down; One or more phase voltages dropped below the Low AC Voltage Threshold for Low AC Voltage Delay seconds
Possible Causes
- •A fault simulation was enabled with a PC based service tool
- •AC voltage falling below threshold for the duration of the time delay
- •Fault Simulation Feature Is Enabled for the engine speed sensor
- •Governor preload offset percentage too high
- •Improper connections have been made at the generator output terminals
- •Incorrect Threshold Setting Or AVR Settings
- •Low AC voltage fault condition
- •Measured AC output voltage is below 85% of nominal for longer than 10 seconds
- •One or more line-to-neutral phase voltages dropped below low AC voltage threshold for time delay seconds
- •The fault threshold is not set correctly with a PC based service tool
- •The rotating rectifier assembly (diodes CR1 through CR6) is faulty
- •The voltage sense or set-up wiring connection could be incorrect
- •There is a loose connector or the Base board is defective
- •There is an overload
Suggested Actions
- 1Adjust or recalibrate as necessary
- 2Check each diode (CR1 through CR6) per the genset service manual
- 3Check the governor preload offset percentage
- 4Check the load and correct any overload; check operation by disconnecting the load and restarting the generator set
- 5Check threshold settings
- 6Connect InPower
- 7Connect with InPower
- 8If authorized, adjust threshold and time limit values using the Genset Setup menus (page 5-37)
- 9Lower the governor preload offset
- 10Reconnect according to the appropriate reconnection diagram
- 11Refer to the Battle Short Mode description on page 3-57
- 12Repair connections (P18) or replace the Base board if necessary
- 13Reset the threshold to the lowest allowable setting after determining the required operating range
- 14Verify AVR settings by comparing gains, settings, and calibration factors against default calibrations
- 15Verify that excitation inputs P18-1 and P18-2 are connected to the correct generator outputs and check Section 7 for proper connections
- 16Verify that fault simulation is not enabled for the engine speed sensor by connecting to the PCC via InPower
- 17Verify that fault threshold is within the normal operating range for low AC voltage
- 18With a PC based service tool, verify that the related fault simulation is not enabled, or remove battery power from the control to disable fault simulation overrides