1447
UnclassifiedGeneral
What This Code Means
Low AC Voltage (Shutdown); One or more phase voltages dropped to 85% of nominal for more than 10 seconds
Possible Causes
- •Fault Simulation Feature Is Enabled for the engine speed sensor
- •Governor preload offset percentage too high
- •Incorrect Threshold Setting Or AVR Settings
Suggested Actions
- 1Adjust or recalibrate as necessary
- 2Check the governor preload offset percentage
- 3Check threshold settings
- 4Connect InPower
- 5Connect with InPower
- 6Lower the governor preload offset
- 7Verify AVR settings by comparing gains, settings, and calibration factors against default calibrations
- 8Verify that fault simulation is not enabled for the engine speed sensor by connecting to the PCC via InPower
- 9Verify that fault threshold is within the normal operating range for low AC voltage