1447

UnclassifiedGeneral

What This Code Means

Engine will shut down; One or more phase voltages dropped below the Low AC Voltage Threshold for Low AC Voltage Delay seconds

Possible Causes

  • •A fault simulation was enabled with a PC based service tool
  • •AC voltage falling below threshold for the duration of the time delay
  • •Fault Simulation Feature Is Enabled for the engine speed sensor
  • •Governor preload offset percentage too high
  • •Improper connections have been made at the generator output terminals
  • •Incorrect Threshold Setting Or AVR Settings
  • •Low AC voltage fault condition
  • •Measured AC output voltage is below 85% of nominal for longer than 10 seconds
  • •One or more line-to-neutral phase voltages dropped below low AC voltage threshold for time delay seconds
  • •The fault threshold is not set correctly with a PC based service tool
  • •The rotating rectifier assembly (diodes CR1 through CR6) is faulty
  • •The voltage sense or set-up wiring connection could be incorrect
  • •There is a loose connector or the Base board is defective
  • •There is an overload

Suggested Actions

  1. 1Adjust or recalibrate as necessary
  2. 2Check each diode (CR1 through CR6) per the genset service manual
  3. 3Check the governor preload offset percentage
  4. 4Check the load and correct any overload; check operation by disconnecting the load and restarting the generator set
  5. 5Check threshold settings
  6. 6Connect InPower
  7. 7Connect with InPower
  8. 8If authorized, adjust threshold and time limit values using the Genset Setup menus (page 5-37)
  9. 9Lower the governor preload offset
  10. 10Reconnect according to the appropriate reconnection diagram
  11. 11Refer to the Battle Short Mode description on page 3-57
  12. 12Repair connections (P18) or replace the Base board if necessary
  13. 13Reset the threshold to the lowest allowable setting after determining the required operating range
  14. 14Verify AVR settings by comparing gains, settings, and calibration factors against default calibrations
  15. 15Verify that excitation inputs P18-1 and P18-2 are connected to the correct generator outputs and check Section 7 for proper connections
  16. 16Verify that fault simulation is not enabled for the engine speed sensor by connecting to the PCC via InPower
  17. 17Verify that fault threshold is within the normal operating range for low AC voltage
  18. 18With a PC based service tool, verify that the related fault simulation is not enabled, or remove battery power from the control to disable fault simulation overrides