1469
UnclassifiedGeneral
What This Code Means
Measured speed and measured AC output frequency do not agree; Engine shutdown
Possible Causes
- •Faulty Magnetic Pick-up
- •Fly Wheel Teeth Number Is Incorrectly Set
- •Flywheel teeth number is incorrectly set
- •Incorrect Engine Speed Data
- •Incorrect flywheel teeth configuration setup
- •Measured engine speed and measured alternator AC output frequency do not agree
- •Speed Hz Match conflict shutdown fault condition active for the duration of the time delay
- •Speed and AC output frequency mismatch
- •Speed/frequency conflict active for the duration of the time delay
Suggested Actions
- 1Access the Flywheel Teeth setup screen through the Operator Panel and ensure that the PCC is set up with the correct number of engine flywheel teeth.
- 2Check the genset setup for number of flywheel teeth
- 3If the MPU tests satisfactorily, then check the voltage output of the board at J11-9 (MPU +) and J11-10 (MPU -).
- 4Inspect the MPU wires/connector pins for shorts and open circuits.
- 5Refer to the engine service manual to correct.
- 6Remove the MPU connectors and check for 3.5 to 15 VAC at the MPU while cranking.
- 7Through the operator panel verify the engine speed by going to Engine Data > Engine Speed.