1689
UnclassifiedGeneral
What This Code Means
Fault Code 1689 (Clock Not Set) becomes active; Real Time Clock (RTC) parameters reset to 00:00 (HH:MM) for Time and 00/00/00 (MM/DD/YY) for Date
Possible Causes
- •Battery power lost for over 1 hour when battery is disconnected or dead
- •Battery power recycled with Exercise Scheduler function enabled
- •Battery power removed
- •PCC1302 control system is not in 'Auto' mode
- •PCC1302 controller entered sleep mode
- •Power supplied to the control again
- •Power to the Real Time Clock (RTC) chip on the base board has been lost
- •RTC (Real Time Clock) is not set (Fault 1689 active)
- •RTC accuracy lost
- •Real time clock (RTC) not set after enabling exercise function
- •Real time clock is not set while exercise scheduler function is enabled
- •SLEEP mode enabled (resets the RTC)
- •Trim 'Scheduler Prog x Enable' is not set to Enable
Suggested Actions
- 1Acknowledge the fault (if the fault clears after being acknowledged, the control is OK)
- 2Acknowledge the fault code to check if it clears
- 3Disable SLEEP mode
- 4If exercise scheduler function is not required, disable the function via HMI211 or service tool
- 5If exercise scheduler function is required, set and save the real time clock
- 6On the operator panel, go to Setup > Clock Setup and set the RTC clock appropriately
- 7Reapply battery power to the control
- 8Set PCC1302 control system to 'Auto' mode
- 9Set the RTC to clear Fault 1689
- 10Set the correct date, time, and clock cycle (AM/PM)
- 11Set trim 'Scheduler Prog x Enable' to Enable