1689

UnclassifiedGeneral

What This Code Means

Fault Code 1689 (Clock Not Set) becomes active; Real Time Clock (RTC) parameters reset to 00:00 (HH:MM) for Time and 00/00/00 (MM/DD/YY) for Date

Possible Causes

  • •Battery power lost for over 1 hour when battery is disconnected or dead
  • •Battery power recycled with Exercise Scheduler function enabled
  • •Battery power removed
  • •PCC1302 control system is not in 'Auto' mode
  • •PCC1302 controller entered sleep mode
  • •Power supplied to the control again
  • •Power to the Real Time Clock (RTC) chip on the base board has been lost
  • •RTC (Real Time Clock) is not set (Fault 1689 active)
  • •RTC accuracy lost
  • •Real time clock (RTC) not set after enabling exercise function
  • •Real time clock is not set while exercise scheduler function is enabled
  • •SLEEP mode enabled (resets the RTC)
  • •Trim 'Scheduler Prog x Enable' is not set to Enable

Suggested Actions

  1. 1Acknowledge the fault (if the fault clears after being acknowledged, the control is OK)
  2. 2Acknowledge the fault code to check if it clears
  3. 3Disable SLEEP mode
  4. 4If exercise scheduler function is not required, disable the function via HMI211 or service tool
  5. 5If exercise scheduler function is required, set and save the real time clock
  6. 6On the operator panel, go to Setup > Clock Setup and set the RTC clock appropriately
  7. 7Reapply battery power to the control
  8. 8Set PCC1302 control system to 'Auto' mode
  9. 9Set the RTC to clear Fault 1689
  10. 10Set the correct date, time, and clock cycle (AM/PM)
  11. 11Set trim 'Scheduler Prog x Enable' to Enable