1915
UnclassifiedGeneral
What This Code Means
Generator set phase rotation is incorrect
Possible Causes
- •Genset Voltage Sensing Connections are Incorrectly Wired at the Base Board
Suggested Actions
- 1If the nominal voltage is 600 VAC or lower, ensure that the voltage sensing connections are correct.
- 2If the phase rotation and/or voltage are not correct, re-check the wiring.
- 3Measure the phase rotation and voltage input into the base board from the Generator set at: L1, J22-1; L2, J22-2; L3, J22-3 (voltage should match nominal voltage, and phase rotation should be 'L1 – L2 – L3').