2335

UnclassifiedGeneral

What This Code Means

Immediate genset shutdown; Battle Short mode suspended; Status indicator lamp flashes shutdown fault code

Possible Causes

  • •Clogged fuel filter
  • •Control board is defective
  • •Control has loss voltage sensing or lost zero cross sensing
  • •Critical shutdown fault generated
  • •Excitation Fault (Loss of Voltage Sense)
  • •Excitation coil is defective
  • •Excitation coil isn’t charged
  • •Genset is not capable of reaching rated speed
  • •Incorrect fuel stop position
  • •Incorrectly configured parameter
  • •Loss of voltage or frequency sensing from the generator
  • •Loss of zero cross detection
  • •Malfunctioning fuel actuators
  • •The wire harness is defective
  • •There may be problems with the load
  • •Wiring issue

Suggested Actions

  1. 1Check alternator voltage sense and excitation leads for shorts or opens
  2. 2Check load for shorts
  3. 3Contact an authorized service center for assistance
  4. 4Ensure that the configuration of the 'Lost AC Voltage Threshold' parameter is set appropriately for the application by navigating to Setup > OEM Setup > OEM ALT Setup > Lost AC Voltage Threshold on the operator panel
  5. 5Flash the excitation coil: Remove Field Coil + and Field Coil – leads from alternator. Using a 12 VDC power supply, touch positive terminal to Field Coil + and negative terminal to Field Coil − briefly, repeating three times. Reconnect leads, reset control, and restart genset. If genset fails to operate correctly, repeat with a 24 VDC power supply.
  6. 6Remove Field Coil + and Field Coil – leads from the alternator and check continuity between Field Coil + and Field Coil − to verify reading is within alternator specifications.
  7. 7Remove the AC Sense harness (J22) and check continuity of all wires. Repair the harness as needed, reset the control, and restart the genset. Check continuity between the following leads. If resistance is greater than 200 Ohms, repair the harness.
  8. 8Replace the control board module.
  9. 9Verify genset set-up by manually running genset to ensure it reaches rated speed. Correct potential problems such as clogged fuel filter, incorrect fuel stop position, or malfunctioning fuel actuators, then reset control and restart genset.
  10. 10Verify that the load contains no shorts. Using a DMM check for shorts between each of the J22 pins. It also may be helpful to disconnect all load lines and start the genset. If the genset runs with no load, that could be load lines are shorted. Refer to the reconnection drawings in Section 7 as a reference.