2621

UnclassifiedGeneral

What This Code Means

Analog input #2 fault is active

Possible Causes

  • •Analog Input #2 active state selection parameter is configured incorrectly
  • •Condition for which Analog Input #2 is configured is active
  • •Incorrectly wired, or open circuit or short circuit in the wiring at J11-3 and J11-4

Suggested Actions

  1. 1After the issue is resolved, press the Reset button on the Operator Panel in order to clear the fault
  2. 2Check the condition for which Analog Input #2 has been configured for
  3. 3Check the wiring at J11-3 (reference input 1) and J11-4 (switch input) for an open circuit, short circuit, or a miswired condition
  4. 4With InPower or through the Operator Panel check the switch input setting (active closed or active open) for Analog Input #2 and ensure it is correctly set