2632
UnclassifiedGeneral
What This Code Means
Discrete input #12 fault is active
Possible Causes
- •Condition for which Discrete Input #12 is configured is active
- •Discrete Input #12 Active State Selection Parameter is configured incorrectly
- •Faulty switch connector(s)
- •Faulty switch unit
- •Incorrectly wired; or open circuit or short circuit in the wiring
Suggested Actions
- 1Check the condition for which Discrete Input #12 has been configured for
- 2Check the switch unit's connection at the plug for an adequate connection, short circuit, open circuit, or a wiring mismatch at the switch connector end
- 3Check the wiring at J4-7 (switch input 1) and J4-8 (reference input) for an open circuit, short circuit, or a miswired condition
- 4Inspect the switch and the harness connector pins for bent or broken pins, pushed back or expanded pins, moisture or corrosion, missing or damaged connector seals, or dirt or debris
- 5Measure the resistance of the switch (< 10 ohms for closed; > 100 Kohms for open) and replace if reading incorrectly (shorted or open circuit)
- 6Press the Reset button on the Operator Panel in order to clear the fault
- 7Visually inspect the switch for proper operation, intended range of movement, and functionality; replace the switch unit if defects or physical damage are detected