2677

UnclassifiedGeneral

What This Code Means

Generator set continues to run after receiving shutdown command from the controller

Possible Causes

  • •Generator Set is operating in a Fuel Rich Environment
  • •Governor Failure
  • •Keyswitch Short
  • •Stuck Fuel Shut-off Actuator

Suggested Actions

  1. 1Check for corroded, bent, broken, pushed back, expanded, or loose pins
  2. 2Check for corroded, bent, broken, pushed back, expanded, or loose pins.
  3. 3Check that the fuel shut-off valve is not mechanically stuck. Use a light tapping with a plastic or rubber mallet to dislodge a stuck actuator.
  4. 4Check that the fuel shut-off valve is not mechanically stuck; lightly tap with a plastic or rubber mallet to dislodge a stuck actuator
  5. 5Check the wiring harness for damage, shorts, or abrasions. Repair as necessary
  6. 6Check the wiring harness for damage, shorts, or abrasions. Repair as necessary.
  7. 7Check ventilation and ventilate area to disperse combustible gasses
  8. 8Check ventilation. Ventilate area to disperse combustible gasses.
  9. 9Refer to the engine service manual
  10. 10Refer to the engine service manual.

ASK RUDY ABOUT THIS FAULT

Get a diagnosis walkthrough for 2677 on your specific Cummins unit — cited to the OEM manual, not a forum guess.

GET THE ANSWER

Free account required — we'll bring your question with you.