2677

UnclassifiedGeneral

What This Code Means

Generator set continues to run after receiving shutdown command from the controller

Possible Causes

  • •Generator Set is operating in a Fuel Rich Environment
  • •Governor Failure
  • •Keyswitch Short
  • •Keyswitch relay stuck closed
  • •Stuck Fuel Shut-off Actuator
  • •Stuck fuel actuator
  • •Stuck fuel shutoff valve

Suggested Actions

  1. 1Activate either emergency stop switch to open the keyswitch relay
  2. 2Check for a stuck fuel actuator and fuel shutoff valve
  3. 3Check for corroded, bent, broken, pushed back, expanded, or loose pins
  4. 4Check that the fuel shut-off valve is not mechanically stuck. Use a light tapping with a plastic or rubber mallet to dislodge a stuck actuator.
  5. 5Check that the fuel shut-off valve is not mechanically stuck; lightly tap with a plastic or rubber mallet to dislodge a stuck actuator
  6. 6Check the keyswitch relay operation and make sure it isn't stuck closed
  7. 7Check the wiring harness for damage, shorts, or abrasions. Repair as necessary
  8. 8Check ventilation and ventilate area to disperse combustible gasses
  9. 9Check ventilation. Ventilate area to disperse combustible gasses.
  10. 10Consult the engine service manual for other possible causes / solutions
  11. 11Refer to the engine service manual
  12. 12Check ventilation.
  13. 13Ventilate area to disperse combustible gasses.