2677
UnclassifiedGeneral
What This Code Means
Generator set continues to run after receiving shutdown command from the controller
Possible Causes
- •Generator Set is operating in a Fuel Rich Environment
- •Governor Failure
- •Keyswitch Short
- •Keyswitch relay stuck closed
- •Stuck Fuel Shut-off Actuator
- •Stuck fuel actuator
- •Stuck fuel shutoff valve
Suggested Actions
- 1Activate either emergency stop switch to open the keyswitch relay
- 2Check for a stuck fuel actuator and fuel shutoff valve
- 3Check for corroded, bent, broken, pushed back, expanded, or loose pins
- 4Check that the fuel shut-off valve is not mechanically stuck. Use a light tapping with a plastic or rubber mallet to dislodge a stuck actuator.
- 5Check that the fuel shut-off valve is not mechanically stuck; lightly tap with a plastic or rubber mallet to dislodge a stuck actuator
- 6Check the keyswitch relay operation and make sure it isn't stuck closed
- 7Check the wiring harness for damage, shorts, or abrasions. Repair as necessary
- 8Check ventilation and ventilate area to disperse combustible gasses
- 9Check ventilation. Ventilate area to disperse combustible gasses.
- 10Consult the engine service manual for other possible causes / solutions
- 11Refer to the engine service manual
- 12Check ventilation.
- 13Ventilate area to disperse combustible gasses.