2888
UnclassifiedGeneral
What This Code Means
AUX 101 1 Analog/Switch input #7 fault is active
Possible Causes
- •Aux 101 1 Analog Input #7 active state selection parameter is configured incorrectly
- •Condition for which Analog/Switch Input #7 is configured for is active
- •Faulty switch connector(s) (inadequate connection, short circuit, open circuit, or wiring mismatch at the switch connector end)
- •Faulty switch unit (physical defects, physical damage, shorted, or open circuit)
Suggested Actions
- 1Check switch connection at the plug for an adequate connection, short circuit, open circuit, or wiring mismatch
- 2Disconnect wiring harness and test resistance between switch output leads and base board input leads (should be < 10 ohms)
- 3Measure switch resistance (< 10 ohms for closed; > 100 Kohms for open) and replace if reading incorrectly (shorted or open circuit)
- 4Press the Reset button on the operator panel to clear the fault after resolving the condition
- 5Test resistance from switch output leads to all other pins in harness connector (should be > 100k ohms)
- 6Verify and adjust the switch input setting (active closed or active open) via InPower service tool or operator panel under Setup > Aux 101 Setup
- 7Verify the condition for which Analog/Switch Input #7 has been configured
- 8Visually inspect the switch for proper operation, intended range of movement, and physical damage/defects; replace switch unit if needed