2896
UnclassifiedGeneral
What This Code Means
Generator set shutdown; Devices fail to properly communicate over the network; Network device exhibiting network issues; Device not awake / missing heartbeat LED blinking
Possible Causes
- •A critical PCCNet device has failed
- •Critical PCCNet device failure
- •Critical PCCnet device failure
- •Faulty network device
- •Grounding loop or ground referencing issue for remotely mounted and powered network
- •Incorrect connection polarity (e.g., RS485+ / RS485- swapped)
- •Incorrect network wire
- •Insufficient voltage at device input (less than 12-24 V)
- •Noise (EMI) issue
- •Open or short circuits in network cable connections
- •Shield grounded at more than one point
Suggested Actions
- 1Check network cable connections for open or short circuits
- 2Correct EMI issue
- 3Correct grounding issue
- 4Ensure correct network connection polarity (Control RS485+ to Annunciator RS485+ and Control RS485- to Annunciator RS485-)
- 5Ensure network device has sufficient voltage (12-24 V) measured at the input of the device
- 6Ensure network shield is grounded at one point ONLY
- 7Refer to PCCNet device manual for line limitations and cable requirements
- 8Replace network wire with required network wire
- 9Replace the network device
- 10Replace the network wire with the required network wire
- 11Test by connecting PCCNet device close (2-5 FT) to base board using base board power supply (TB1-5 B+ and TB1-3 ground) with required network wire
- 12Verify device is awake and heartbeat LED blinks every 1 second