2896

UnclassifiedGeneral

What This Code Means

Generator set shutdown; Devices fail to properly communicate over the network; Network device exhibiting network issues; Device not awake / missing heartbeat LED blinking

Possible Causes

  • •A critical PCCNet device has failed
  • •Critical PCCNet device failure
  • •Critical PCCnet device failure
  • •Faulty network device
  • •Grounding loop or ground referencing issue for remotely mounted and powered network
  • •Incorrect connection polarity (e.g., RS485+ / RS485- swapped)
  • •Incorrect network wire
  • •Insufficient voltage at device input (less than 12-24 V)
  • •Noise (EMI) issue
  • •Open or short circuits in network cable connections
  • •Shield grounded at more than one point

Suggested Actions

  1. 1Check network cable connections for open or short circuits
  2. 2Correct EMI issue
  3. 3Correct grounding issue
  4. 4Ensure correct network connection polarity (Control RS485+ to Annunciator RS485+ and Control RS485- to Annunciator RS485-)
  5. 5Ensure network device has sufficient voltage (12-24 V) measured at the input of the device
  6. 6Ensure network shield is grounded at one point ONLY
  7. 7Refer to PCCNet device manual for line limitations and cable requirements
  8. 8Replace network wire with required network wire
  9. 9Replace the network device
  10. 10Replace the network wire with the required network wire
  11. 11Test by connecting PCCNet device close (2-5 FT) to base board using base board power supply (TB1-5 B+ and TB1-3 ground) with required network wire
  12. 12Verify device is awake and heartbeat LED blinks every 1 second