2942
UnclassifiedGeneral
What This Code Means
The genset has failed to transition to Battle Short mode or Delayed Shutdown mode
Possible Causes
- •Battle Short Or Delayed Shutdown Is Not Enabled In The Genset Control
- •Battle Short Switch or Battle Short Switch (Modbus) is active, but Battle Short Enable is not set to Enable
- •Battle Short Switch or Battle Short Switch (Modbus) is active, but the ECM is not set to enable Battle Short mode (Core 2 ECMs only)
- •Battle Short is not enabled in the baseboard
Suggested Actions
- 1Connect to the baseboard with InPower and set 'Shutdown Manual Override' under 'Engine Protection' to 'Enable'
- 2Contact your local distributor for assistance
- 3Ensure Battle Short Enable is set to Enable
- 4Ensure one of the configurable inputs is set up to activate Battle Short mode (e.g., Configurable Input #1 = Battle Short) and activate the configurable input (e.g., with a ground input)
- 5Ensure the ECM is set to enable Battle Short mode (Core 2 ECMs only)
- 6Have Battle Short mode set up at the factory or by an authorized service representative
- 7Through the operator panel, verify that the 'Battle Short' parameter is set to enable (go to Setup > OEM Setup > OEM Genset Setup > Battle Short and set to enable if required)
- 8Through the operator panel, verify that the 'Delayed Shutdown' parameter is set to enable (go to Setup > OEM Setup > OEM Genset Setup > Delayed Shutdown and set to enable if required)