2942

UnclassifiedGeneral

What This Code Means

The genset has failed to transition to Battle Short mode or Delayed Shutdown mode

Possible Causes

  • •Battle Short Or Delayed Shutdown Is Not Enabled In The Genset Control
  • •Battle Short Switch or Battle Short Switch (Modbus) is active, but Battle Short Enable is not set to Enable
  • •Battle Short Switch or Battle Short Switch (Modbus) is active, but the ECM is not set to enable Battle Short mode (Core 2 ECMs only)
  • •Battle Short is not enabled in the baseboard

Suggested Actions

  1. 1Connect to the baseboard with InPower and set 'Shutdown Manual Override' under 'Engine Protection' to 'Enable'
  2. 2Contact your local distributor for assistance
  3. 3Ensure Battle Short Enable is set to Enable
  4. 4Ensure one of the configurable inputs is set up to activate Battle Short mode (e.g., Configurable Input #1 = Battle Short) and activate the configurable input (e.g., with a ground input)
  5. 5Ensure the ECM is set to enable Battle Short mode (Core 2 ECMs only)
  6. 6Have Battle Short mode set up at the factory or by an authorized service representative
  7. 7Through the operator panel, verify that the 'Battle Short' parameter is set to enable (go to Setup > OEM Setup > OEM Genset Setup > Battle Short and set to enable if required)
  8. 8Through the operator panel, verify that the 'Delayed Shutdown' parameter is set to enable (go to Setup > OEM Setup > OEM Genset Setup > Delayed Shutdown and set to enable if required)