2892
UnclassifiedGeneral
What This Code Means
Discrete input #2 fault is active; Fault Code 2892 does not clear after pressing the Reset button
Possible Causes
- •Aux 102 1 Discrete Input #2 Active State Selection Parameter is configured incorrectly
- •Aux 102 1 Discrete Input #2 active state selection parameter is configured incorrectly
- •Condition for which Discrete Input #2 is configured for is active
- •Condition for which Discrete Input #2 is configured is active
- •Damaged or contaminated switch/harness connector pins (bent, broken, pushed back, expanded, moisture, corrosion, missing/damaged seals, dirt/debris)
- •Discrete Input #2 active state selection parameter is configured incorrectly (e.g., active close vs active open logic inverted)
- •Faulty switch connector or wiring
- •Faulty switch connector(s) (inadequate connection, short circuit, open circuit, wiring mismatch)
- •Faulty switch connector(s) (inadequate connection, short circuit, open circuit, wiring mismatch, pin damage, moisture/corrosion, missing/damaged seals, or debris)
- •Faulty switch unit
- •Faulty switch unit (defects, physical damage, shorted or open circuit)
- •Faulty switch unit (defects, physical damage, shorted, or open circuit)
Suggested Actions
- 1Check switch connector plug for adequate connection, short circuit, open circuit, or wiring mismatch
- 2Check switch unit plug connection for adequate connection, short circuit, open circuit, or wiring mismatch
- 3Check switch unit's connection at the plug for adequate connection, short circuit, open circuit, or wiring mismatch
- 4Inspect switch and harness connector pins for bent, broken, pushed back, or expanded pins
- 5Inspect switch and harness connector pins for bent, broken, pushed back, or expanded pins, moisture or corrosion, missing or damaged connector seals, and dirt or debris
- 6Inspect switch and harness connector pins for bent, broken, pushed back, or expanded pins, moisture, corrosion, missing/damaged seals, or dirt and debris
- 7Inspect switch and harness connectors for moisture, corrosion, missing/damaged connector seals, or dirt/debris
- 8Measure switch resistance (< 10 ohms for closed; > 100 Kohms for open) and replace switch if reading incorrectly
- 9Measure switch resistance (< 10 ohms for closed; > 100 Kohms for open) and replace the switch if reading incorrectly (shorted or open circuit)
- 10Press the Reset button on the operator panel to clear the fault after resolving the issue
- 11Verify and correct switch input setting (active closed or active open) using InPower service tool or operator panel under Setup > Aux 101 Setup
- 12Verify and correct the switch input setting (active closed or active open) for Discrete Input #2 via InPower service tool or operator panel under Setup > Aux 101 Setup
- 13Verify and correct the switch input setting (active closed or active open) using the InPower service tool or operator panel under Setup > Aux 101 Setup
- 14Verify the condition for which Discrete Input #2 has been configured
- 15Verify the condition for which Discrete Input #2 has been configured and press the Reset button on the operator panel after resolving the issue
- 16Verify the condition for which Discrete Input #2 has been configured and resolve the underlying issue
- 17Visually inspect switch for proper operation, intended range of movement, functionality, defects, or physical damage; replace switch unit if defects are found
- 18Visually inspect switch for proper operation, range of movement, defects, or physical damage, and replace if necessary
- 19Visually inspect the switch for proper operation, intended range of movement, defects, or physical damage, and replace if necessary
Related Cummins Fault Codes