2815
UnclassifiedGeneral
What This Code Means
Generator set dumps its electrical load; Generator set KW output exceeds the Overload Threshold for the Overload Set Time; Output frequency of the generator set drops below the Under-frequency Offset for the Under-frequency Set Time
Possible Causes
- •Another active fault is set to Derate
- •Generator set KW output exceeds Overload Threshold for Overload Set Time
- •Generator set output frequency drops below Under-frequency Offset for Under-frequency Set Time
- •Incorrect CTs or CT Connections
- •Incorrect CTs or CT connections
- •Overload Set Time or Under-frequency Set Time is set too low
- •Under-frequency Offset is set too low
Suggested Actions
- 1Check the CTs, CT Connections, and CT ratio
- 2Check the CTs, CT connections, and CT ratio
- 3Go to Setup > Genset Setup on the operator panel and set the Overload Set Time and Under-frequency Set Time parameters appropriately for the application
- 4Go to Setup > Genset Setup on the operator panel and set the Under-frequency Offset parameter appropriately for the application
- 5Refer to the section on Current Transformer Installation or reference event/fault code 2814 and event/fault code 2815
- 6Troubleshoot other active fault(s) set to Derate
- 7Troubleshoot the other active fault(s) that are set to Derate