1433
UnclassifiedCooling
What This Code Means
Engine fails to start; Red Shutdown status LED illuminated; Shutdown condition indicated on display; Engine coolant temperature is below the low coolant temperature warning threshold; Coolant level sensor signal is showing a low coolant level for greater than 10 seconds; Coolant level low warning; Coolant level low shutdown; Low fuel warning; Low fuel shutdown; Unconditional engine stop, bypassing any time delay to stop; Bypassed shutdown fault while the generator set was in Battle Short mode; Local or remote Emergency Stop has been activated; Fail to shutdown
Possible Causes
- •Ambient temperature too cold for specified generator set
- •Blockage in coolant system
- •Coolant heater malfunction or not installed
- •Critical shutdown fault generated
- •Emergency Stop button is pressed
- •Event/fault 1416 activated as a result of another active shutdown fault while the PowerCommand 3.3 control is operating in Battle Short mode
- •Faulty Connection Or Faulty Emergency Stop Switch
- •Faulty or inoperable switch
- •Local Emergency Stop button pressed
- •Local or remote Emergency Stop has been activated
- •Low coolant
- •Low fuel level
- •Open circuit condition in the connection/wiring from the Local Emergency Stop switch to the control
- •Remote Emergency Stop button pressed
- •The Local Emergency Stop Button Has Been Activated
Suggested Actions
- 1Add the manufacturer's prescribed fuel.
- 2Allow the engine to cool down completely before proceeding with checks
- 3Check that the Emergency Stop button is working correctly
- 4Check the Emergency Stop button, and verify that it is working properly (closed relay when pulled out, open relay when depressed)
- 5Check the Input # requirements and correct if possible
- 6Contact your Cummins service representative
- 7Contact your local dealer if repair or replacement is required.
- 8If the coolant level is too low, add coolant per specifications.
- 9If the engine can be stopped, allow the engine to cool down completely before proceeding
- 10Investigate and remedy the cause of the emergency stop before attempting a reset and start
- 11Make sure the coolant heater is installed and powered
- 12Make sure the generator set meets its performance specifications
- 13Press the Auto or Manual Run button as previously determined
- 14Press the Off button
- 15Press the Off button on the Operator Panel to acknowledge this action
- 16Press the Reset button
- 17Pull (or twist and pull) the Emergency Stop button out
- 18Pull the Local Emergency stop button out
- 19Push this button in for Emergency Shutdown of the engine.
- 20Remove the switch and verify proper switch operation. If either of the following conditions is demonstrated, the switch is defective: When the float is at the bottom of the switch, the wires do not show continuity; When the float is raised, the wires do not show an open circuit.
- 21Reset the local/remote Emergency Stop button: De-activate (disable) the Emergency Stop button, press the Stop button, press the Reset button, and select the desired operating mode (manual or auto)
- 22Select Manual or Auto as required
- 23Stop the engine and allow the engine to cool down.
- 24Troubleshoot the shutdown fault that is causing the generator set to shut down
- 25Verify the connection/wiring from the Local Emergency Stop switch to the control for an open circuit condition (check J25-2 Input and J25-6 Ground)
- 26Visually inspect and verify that the engine coolant is at the appropriate level.