1312

UnclassifiedCooling

What This Code Means

Engine has overheated; Intake manifold temperature has risen above the shutdown trip point; Derate lamp active; High Intake Manf 1 temp message displayed; Engine hot shutdown has occurred; Cooldown timers were bypassed; Warning lamp active; Engine Hot Shut Down message displayed; Communication between the engine control (ECM) and the PowerCommand 3.3 control has been severed; Shutdown lamp active; CAN Data Link Failure message displayed; Control is in Battle Short mode; Battle Short Active message displayed; Triggered configurable customer input alarm (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault)

Possible Causes

  • •Active E-Stop button
  • •Battle Short mode manual activation to bypass fault shutdowns during emergencies
  • •Configurable input condition met
  • •External wiring problem
  • •High ambient temperature
  • •Large load
  • •Operator pressed the Emergency Switch before the generator set completed the cooldown operation
  • •Operator pressed the Stop button before the generator set completed the cooldown operation
  • •Optional configurable selection input activated
  • •Optional customer selection
  • •The nature of the fault is an optional configurable selection

Suggested Actions

  1. 1Allow the engine to cool down completely before proceeding (if the engine can be stopped)
  2. 2Change fault default values using the Genset Setup menus
  3. 3Change the display name using up to 32 characters
  4. 4Check the Input requirement details and correct the condition
  5. 5Contact authorized service technician if in doubt
  6. 6Ensure the E-Stop button is not active
  7. 7If possible, investigate any fault codes that are being bypassed
  8. 8If the Fault Input Active State select is set to active close, check to see if GND is at the fault input terminal; if GND is present, check external wiring
  9. 9If the Fault Input Active State select is set to active open, check to see if GND is not at the fault input terminal; if GND is not present, check external wiring
  10. 10Program fault functions (Event, Warning, or Shutdown level) using a service tool or the operator panel
  11. 11Program input functions using the InPower service tool or by accessing the Setup menu
  12. 12Reset the Local/Remote Emergency Stop
  13. 13Review fault code 151 correction list for other possible causes
  14. 14Run the generator set at 10% or less load for three minutes before engine shutdown to avoid hot shutdowns