343
UnclassifiedCooling
What This Code Means
Hardware Failure Warning active; EEPROM Write Failure Warning active; Unsuccessful attempt to save a trim; The Synchronizing System is not in Auto mode
Possible Causes
- •Calibration Checksum Warning (Fault Code 2416) is active
- •EEPROM Write Failure Warning (Fault Code 353) is active
- •Utility Bus AC Metering Failure (Fault Code 1335) is active
- •Generator Bus AC Metering Failure (Fault Code 1335) is active
- •The hardware version is not compatible with the software version
- •The current value in RAM memory (to-be-written value) does not match its post-written value in EEPROM
- •Attempt to save a trim by using either InPower or the LCD display is not successful
- •The SYNC1320 master synchronizer fails to automatically save data on a periodic basis
- •Misoperation of relevant terminal blocks (TB10-6) on the SYNC1320 master synchronizer and related switches
- •Faulty cabling from the switches to the terminal blocks
- •Control switch operation is not OK
Suggested Actions
- 1Identify which of the faults is active by observing the fault displayed on the control panel or observing the lamps on the SYNC1320 control board, or by using InPower
- 2Take corrective steps for the active specific faults
- 3Cycle power to the SYNC1320 master synchronizer
- 4If the problem continues, replace the control board
- 5Clear the fault by cycling power to the SYNC1320 master synchronizer
- 6Clear the fault by resetting the processor via an InPower initial calibration
- 7Verify if working in non-Auto mode is intentional
- 8Check relevant terminal blocks (TB10-6) on the SYNC1320 master synchronizer and related switches for misoperation
- 9Check cabling from the switches to the terminal blocks
- 10Make sure the control switch operation is OK
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for 343 on your specific Cummins unit — cited to the OEM manual, not a forum guess.
TRY IT FREE