1317

UnclassifiedCooling

What This Code Means

Coolant level sensor signal is showing a low coolant level for greater than 10 seconds; Coolant level low warning; Coolant level low shutdown; Low fuel warning; Low fuel shutdown; Unconditional engine stop, bypassing any time delay to stop; Engine has overheated; Intake manifold temperature has risen above the shutdown trip point; Derate lamp active; High Intake Manf 1 temp message displayed; Engine hot shutdown has occurred; Cooldown timers were bypassed; Warning lamp active; Engine Hot Shut Down message displayed; Communication between the engine control (ECM) and the PowerCommand 3.3 control has been severed; Shutdown lamp active; CAN Data Link Failure message displayed; Control is in Battle Short mode; Battle Short Active message displayed; Triggered configurable customer input alarm (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault)

Possible Causes

  • •Active E-Stop button
  • •Battle Short mode manual activation to bypass fault shutdowns during emergencies
  • •Configurable input condition met
  • •External wiring problem
  • •Faulty or inoperable switch
  • •High ambient temperature
  • •Large load
  • •Local Emergency Stop button pressed
  • •Low coolant
  • •Low fuel level
  • •Operator pressed the Emergency Switch before the generator set completed the cooldown operation
  • •Operator pressed the Stop button before the generator set completed the cooldown operation
  • •Optional configurable selection input activated
  • •Optional customer selection
  • •Remote Emergency Stop button pressed
  • •The nature of the fault is an optional configurable selection

Suggested Actions

  1. 1Add the manufacturer's prescribed fuel.
  2. 2Allow the engine to cool down completely before proceeding (if the engine can be stopped)
  3. 3Change the display name using up to 32 characters
  4. 4Check the Input requirement details and correct the condition
  5. 5Contact authorized service technician if in doubt
  6. 6Contact your local dealer if repair or replacement is required.
  7. 7Ensure the E-Stop button is not active
  8. 8If possible, investigate any fault codes that are being bypassed
  9. 9If the Fault Input Active State select is set to active close, check to see if GND is at the fault input terminal; if GND is present, check external wiring
  10. 10If the Fault Input Active State select is set to active open, check to see if GND is not at the fault input terminal; if GND is not present, check external wiring
  11. 11If the coolant level is too low, add coolant per specifications.
  12. 12Program fault functions (Event, Warning, or Shutdown level) using a service tool or the operator panel
  13. 13Program input functions using the InPower service tool or by accessing the Setup menu
  14. 14Push this button in for Emergency Shutdown of the engine.
  15. 15Remove the switch and verify proper switch operation. If either of the following conditions is demonstrated, the switch is defective: When the float is at the bottom of the switch, the wires do not show continuity; When the float is raised, the wires do not show an open circuit.
  16. 16Reset the Local/Remote Emergency Stop
  17. 17Review fault code 151 correction list for other possible causes
  18. 18Run the generator set at 10% or less load for three minutes before engine shutdown to avoid hot shutdowns
  19. 19Stop the engine and allow the engine to cool down.
  20. 20Visually inspect and verify that the engine coolant is at the appropriate level.