1416
UnclassifiedGeneral
What This Code Means
Bypassed shutdown fault while the generator set was in Battle Short mode; Local or remote Emergency Stop has been activated; Fail to shutdown
Possible Causes
- •A Shutdown Fault was Bypassed While the Battle Short Feature was Enabled on the Control
- •Active Shutdown fault while operating in battle-short mode
- •Battle Short mode is active
- •Event/fault 1416 activated as a result of another active shutdown fault while the PowerCommand 3.3 control is operating in Battle Short mode
- •Local or remote Emergency Stop has been activated
- •PCC overrides a shutdown fault while Battle Short mode remains active
Suggested Actions
- 1Act upon all shutdown faults immediately
- 2Allow the engine to cool down completely before proceeding with checks
- 3Check that the Emergency Stop button is working correctly
- 4Check the Input # requirements and correct if possible
- 5Click on Save to map a configurable input to the Battle Short Switch
- 6Click on Setup > Configurable I/O folders
- 7If the engine can be stopped, allow the engine to cool down completely before proceeding
- 8Open InPower with the security dongle attached and click on the control in the left side of the window
- 9Put the PCC in Off mode
- 10Reset the local/remote Emergency Stop button: De-activate (disable) the Emergency Stop button, press the Stop button, press the Reset button, and select the desired operating mode (manual or auto)
- 11Set the Setup Mode Enable parameter to Enable in order to enter Setup mode
- 12Troubleshoot the other shutdown fault(s) that are causing the generator set to display event/fault code 1416
- 13Troubleshoot the shutdown fault that is causing the generator set to shut down
- 14Use the PC-based service tool harness to connect the computer to TB15 on the PCC base board