1311

UnclassifiedGeneral

What This Code Means

Configurable fault input triggered (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault)

Possible Causes

  • •External wiring problem
  • •External wiring short circuit
  • •Grounding of signal input
  • •Optional configurable selection input activated
  • •Optional customer selection
  • •Optional ruptured basin switch installed and activated
  • •The nature of the fault is an optional configurable selection

Suggested Actions

  1. 1Change fault default values using the Genset Setup menus
  2. 2Change the display name using up to 32 characters
  3. 3Disconnect the signal lead from TB1 (CONFIG INPUT 1 TB1-12) and reset the control
  4. 4If the Fault Input Active State select is set to active close, check to see if GND is at the fault input terminal; if GND is present, check external wiring
  5. 5If the Fault Input Active State select is set to active open, check to see if GND is not at the fault input terminal; if GND is not present, check external wiring
  6. 6If the fault message goes away, inspect and repair the external wiring short circuit
  7. 7Program fault functions (Event, Warning, or Shutdown level) using a service tool or the operator panel