1311
UnclassifiedGeneral
What This Code Means
Configurable fault input triggered (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault)
Possible Causes
- •External wiring problem
- •External wiring short circuit
- •Grounding of signal input
- •Optional configurable selection input activated
- •Optional customer selection
- •Optional ruptured basin switch installed and activated
- •The nature of the fault is an optional configurable selection
Suggested Actions
- 1Change fault default values using the Genset Setup menus
- 2Change the display name using up to 32 characters
- 3Disconnect the signal lead from TB1 (CONFIG INPUT 1 TB1-12) and reset the control
- 4If the Fault Input Active State select is set to active close, check to see if GND is at the fault input terminal; if GND is present, check external wiring
- 5If the Fault Input Active State select is set to active open, check to see if GND is not at the fault input terminal; if GND is not present, check external wiring
- 6If the fault message goes away, inspect and repair the external wiring short circuit
- 7Program fault functions (Event, Warning, or Shutdown level) using a service tool or the operator panel