E-CODE 2099

UnclassifiedElectrical

What This Code Means

Voltage measures more than 40 VAC between Wire 194/Wire 23 and Wire 0

Possible Causes

  • •Mis-wired connection at TB1 & TB2 or in the transfer switch

Suggested Actions

  1. 1Find the mis-wired connection at TB1 & TB2 or in the transfer switch
  2. 2Power cycle the controller and retest, if still present replace the controller and retest