LOW BATTERY ALARM
UnclassifiedElectrical
What This Code Means
Low Battery alarm is on
Possible Causes
- •Battery voltage below 12.2 VDC for one minute
- •Battery voltage drops below 6 VDC during a crank cycle
- •Bad battery
- •Incorrect 120 VAC input connection
Suggested Actions
- 1Check battery conditions
- 2Verify battery voltage is above 12.8 VDC at J2 Pin 5 (Wire 15E)
- 3Inspect and replace battery if faulty
- 4Ensure 120 VAC input is connected at the customer connection box for the battery charger to function.