LOW BATTERY ALARM

UnclassifiedElectrical

What This Code Means

Low Battery alarm is on

Possible Causes

  • Battery voltage below 12.2 VDC for one minute
  • Battery voltage drops below 6 VDC during a crank cycle
  • Bad battery
  • Incorrect 120 VAC input connection

Suggested Actions

  1. 1Check battery conditions
  2. 2Verify battery voltage is above 12.8 VDC at J2 Pin 5 (Wire 15E)
  3. 3Inspect and replace battery if faulty
  4. 4Ensure 120 VAC input is connected at the customer connection box for the battery charger to function.