ALARM #23
UnclassifiedElectrical
What This Code Means
Error LEDs are on (red); Illogical battery parameters
Possible Causes
- •One or more batteries are defective
- •Internal battery test problem
- •Internal battery problem
Suggested Actions
- 1Perform a system shutdown (do not turn the batteries off)
- 2Check that the batteries are working properly
- 3Check to see if the error LEDs are on (red) and identify the defective elements
- 4Check that the communication between the BMS of the batteries and the Cerbo GX is correct
- 5Check that the RJ45 connectors connected between the battery modules are in good condition and tightly tightened
- 6Check that the voltage between the DC terminals of the input of each of the inverters is correct
- 7Turn the batteries off and restart the equipment
- 8Click on the variable 'VE. Reset' to reset the communication
- 9Check that the voltage between the DC terminals of the input of each of the inverters is correct (must have a value between [45 – 52] V)
- 10Check that the communication between the BMS of the batteries and the Cerbo GX is correct by observing the parameters of the battery to check that they are logical