ALARM #21
UnclassifiedGeneral
What This Code Means
MPPT error persists; Red error LEDs are on
Possible Causes
- •Defective MPPT equipment
- •Internal battery problem
- •Defective battery
Suggested Actions
- 1Check that the communication between the Cerbo GX and the MPPT is correct via the VE.Direct connector
- 2Apply a DC supply to the solar input terminals (>55V and >10A)
- 3Verify that the magneto-technical protections are enabled
- 4Verify that the fuses are operational
- 5Replace the MPPT equipment
- 6Perform a system shutdown according to the manual (do not turn the batteries off)
- 7Check that the batteries are working properly
- 8Check to see if the error LEDs are on (red)
- 9Check that the communication between the BMS of the batteries and the Cerbo GX is correct
- 10Check that the voltage between the DC terminals of the input of each of the inverters is correct
- 11Turn the batteries off and restart the equipment
- 12Check that the batteries are working properly and identify defective elements if the red error LEDs are on
- 13Check that the RJ45 connectors connected between the battery modules are in good condition and tightly tightened
- 14Check to see if the error LEDs are on (red) and identify defective elements