15
UnclassifiedElectrical
What This Code Means
Engine will not shut off (Run Light is Off); Over Voltage (controller can not regulate to rated voltage); Under Voltage (controller can not regulate to rated voltage); Undervoltage; Overfrequency; Underfrequency; Excessive Smoke Under Load; Overprime; Overvoltage
Possible Causes
- •Binding in the governor linkage
- •Blocked exhaust system
- •Control plugs not fully seated
- •Dirty or restricted air cleaner
- •Excessive connected loads
- •Faulty field windings
- •Faulty fuel solenoid valve operation
- •Faulty genset control PCB
- •Faulty governor actuator operation
- •Faulty governor controller board
- •Faulty ignition system
- •Faulty magnetic pick-up operation
- •Faulty start/stop switch (local and remote)
- •Fuel supply issues
- •Genset is loaded nearly to full power and a large motor load (such as an air conditioner) cycles on
- •Governor linkage binding
- •Grounded field windings
- •Grounded or shorted main windings
- •Improper field resistance (open to ground)
- •Improper loads
- •Improper quad winding resistance
- •Incorrect battery voltage
- •Incorrect engine speed
- •Incorrect engine speed (frequency)
- •Incorrect gas supply pressure
- •Incorrect loads
- •LPG fuel tank less than half full during cold weather (insufficient vaporization)
- •Large motor load draws up to three or more times its rated power consumption at startup
- •Open or shorted wiring
- •Opens and/or shorts in stator and rotor
- •Overload Condition
- •Poor brush condition and contact
- •Quad leads not fully seated in connector to control
- •Unsecured spark plug cable
- •Use of LPG with more than 2.5 percent butane below 32 °F (0 °C)
- •Worn or malfunctioning engine (low cylinder compression)
Suggested Actions
- 1Check brush condition and contact
- 2Check circuit breaker
- 3Check control
- 4Check engine speed
- 5Check engine speed (frequency)
- 6Check field windings
- 7Check for a blocked exhaust system and service as necessary
- 8Check for binding in the governor linkage
- 9Check for grounded or shorted main windings
- 10Check for proper field resistance reading, open to ground
- 11Check fuel solenoid valve operation
- 12Check fuel supply
- 13Check governor actuator operation
- 14Check loads
- 15Check magnetic pick-up for proper operation
- 16Check output voltage
- 17Check quad winding resistance
- 18Check stator and rotor for opens and/or shorts
- 19Check that control plugs are fully seated
- 20Check that quad leads are fully seated in connector to control
- 21Check the gas supply pressure and adjust as necessary
- 22Check the governor controller board
- 23Check the governor linkage for binding and service as necessary
- 24Conduct a cylinder compression test and service the engine if it is worn or malfunctioning
- 25Conduct the ignition system tests and service as necessary
- 26Fill the LPG fuel tank if less than half full and use HD-5 grade LPG
- 27Inspect and secure the spark plug cable on the spark plugs
- 28Limit the total load to not exceed 80% of the genset kW rating when powering large motor loads
- 29Perform checks in step 01
- 30Replace the genset control PCB
- 31Service the air cleaner
- 32Shut off some loads at times when large motor loads are active
- 33Turn the genset line circuit breaker OFF and run the genset with fewer connected loads
- 34Verify control plugs are fully seated
- 35Verify quad leads are fully seated in connector to control