27
UnclassifiedElectrical
What This Code Means
Loss of AC Sense; Excessive Smoke Under Load; Loss of voltage sense; Loss of quad sense; Engine stopped
Possible Causes
- •AC sense circuitry lack of continuity
- •AC sense transformer resistance out of specification
- •Broken voltage sense leads
- •Control fault
- •External shorts
- •Faulty genset control PCB
- •Fuel supply issue
- •Loose voltage sense leads
- •Mechanical engine damage
- •Overload Condition
- •Rotor resistance open, short, or ground
- •Stator resistance open, short, or ground
Suggested Actions
- 1Check AC output
- 2Check AC sense circuitry (Voltage Sense Input signal to genset control PCB) for continuity
- 3Check battery connection to battery & set
- 4Check battery voltage to set
- 5Check field resistance
- 6Check fuel supply
- 7Check mechanical engine damage
- 8Check resistance of AC sense transformer (H1 to H2 - 309 ohms ± 10%, X1 to X2 - 391 ohms ± 10%)
- 9Check rotor resistance (opens/shorts/grounds)
- 10Check stator resistance
- 11Check stator resistance (opens/shorts/grounds)
- 12Check voltage sense leads
- 13Replace the genset control PCB
- 14Troubleshoot Control
- 15Troubleshoot external shorts