29
UnclassifiedElectrical
What This Code Means
Loss of AC Sense; Engine Stopped; Excessive Smoke Under Load; Loss of voltage sense; Loss of quad sense; Engine stopped
Possible Causes
- •Broken voltage sense leads
- •Control fault
- •External shorts
- •Faulty battery charging system
- •Fuel supply issue
- •Grounded or shorted quad windings
- •Loose voltage sense leads
- •Mechanical engine damage
- •Overload Condition
- •Rotor resistance open, short, or ground
- •Stator resistance open, short, or ground
Suggested Actions
- 1Check AC output
- 2Check battery connection to battery & set
- 3Check battery voltage to set
- 4Check brush condition and contact
- 5Check field resistance
- 6Check field windings
- 7Check for grounded or shorted quad windings
- 8Check for proper field resistance reading, open to ground
- 9Check fuel supply
- 10Check governor actuator operation
- 11Check loads
- 12Check mechanical engine damage
- 13Check output voltage
- 14Check stator resistance
- 15Check stator resistance (opens/shorts/grounds)
- 16Check voltage sense leads
- 17Test the battery charging system and service as necessary
- 18Troubleshoot Control
- 19Troubleshoot external shorts
- 20Verify control plugs are fully seated
- 21Verify quad leads are fully seated in connector to control