00-0AG

UnclassifiedElectrical

What This Code Means

No Output Voltage (Avr) (Genset); No output voltage; No output voltage (Avr) (Genset); High/Low AC Output (Genset); No AC Output Voltage; Unstable Voltage with Stable Engine; Unbalanced Output Voltage; Starts but stops when switch released; Genset starts but stops after switch releases; High/Low AC Output; Unstable Voltage; Unbalanced Generator Output Voltage

Possible Causes

  • Broken wires
  • Loose wires
  • Broken or loose wires
  • Excitor stator failure
  • Control plugs not fully seated
  • Load breaker open
  • Improper output lead connection
  • Sense leads not fully seated in connector to control
  • Incorrect output lead configuration
  • Load breaker not closed
  • AC output to load breakers issue
  • Field breaker CB21 issue
  • Excitor field wiring issue
  • Bridge rectifier issue
  • Voltage regulator issue
  • Residual voltage issue
  • Main rotor issue
  • Main stator issue
  • Incorrect oil level
  • Faulty oil pressure switch

Suggested Actions

  1. 1Check load breaker closed
  2. 2Check for broken or loose wires
  3. 3Check AC output to load breakers
  4. 4Check field breaker CB21
  5. 5Check residual voltage at VR21
  6. 6Check excitor field wiring
  7. 7Check commutating reactor
  8. 8Check reference transformer
  9. 9Check regulating transformer
  10. 10Check bridge rectifier CR21
  11. 11Check field flash
  12. 12Check rotating diodes CR1 to CR6
  13. 13Check voltage regulator VR21
  14. 14Check excitor rotor windings
  15. 15Check main rotor
  16. 16Check main stator
  17. 17Verify load breaker is closed
  18. 18Check exciter field wiring
  19. 19Check rotating diodes CR1 - CR6
  20. 20Check residual voltage