1163

UnclassifiedEmissions

What This Code Means

Malfunction Indicator Lamp (MIL) ON; Adaptive multiplier out of range greater than 30% while running on natural gas; Lean exhaust condition (especially at light load); False lean condition; One bank shows high adaptive and the other is low; One bank shows high adaptive and the other bank shows low adaptive

Possible Causes

  • Heated Oxygen (O2) sensor wires mis-routed and contacting the exhaust manifold
  • Large vacuum leaks
  • Crankcase leaks
  • Faulty EPR (Electronic Pressure Regulator)
  • Faulty fuel mixer
  • Low fuel pressure
  • Faulty fuel regulator
  • Contaminated fuel filter
  • Exhaust leak pulling outside air past the O2 sensor
  • Contaminated or spoiled fuel
  • ECM grounds not clean, tight, or in the proper location
  • Crossed O2 sensor leads
  • Heated oxygen sensor wires mis-routed and contacting the exhaust manifold
  • Exhaust leak pulling outside air into the exhaust past the O2 sensor

Suggested Actions

  1. 1Run the fuel system diagnostic checks
  2. 2Verify heated oxygen sensor wire routing to ensure they are not contacting the exhaust manifold
  3. 3Inspect and repair vacuum leaks and crankcase leaks
  4. 4Inspect and replace faulty EPR or fuel mixer
  5. 5Check fuel pressure, inspect fuel regulator, and replace contaminated fuel filter
  6. 6Inspect and repair exhaust leaks
  7. 7Clean, tighten, and correctly position ECM grounds
  8. 8Trace O2 sensor wires back to their ECMs and correct crossed leads
  9. 9Run the fuel system diagnostic checks before proceeding with further diagnostics
  10. 10Verify ECM grounds are clean, tight, and in the proper location
  11. 11Trace crossed O2 sensor wires back to their ECMs and correct them

Related Power Solutions International Fault Codes