WARNING #8

UnclassifiedElectrical

What This Code Means

The mode of operation at that moment will be shut down immediately; Installation is supplied with a power higher than that which has been configured; Possible internal battery problem; Battery error LEDs are on (red); Incorrect arrangement of phases

Possible Causes

  • Maximum contracted power has been exceeded when the calendar is enabled and configured
  • Defective battery
  • Deterioration of the cells
  • Internal communication failure
  • Incorrect arrangement of phases

Suggested Actions

  1. 1Configure the calendar (refer to Calendar section)
  2. 2Perform a system shutdown without turning the batteries off
  3. 3Check that the batteries are working properly and check if error LEDs are on (red)
  4. 4Check that the communication between the BMS of the batteries and the Cerbo GX is correct
  5. 5Check that the voltage between the DC terminals of the input of each of the inverters is correct
  6. 6Check that the RJ45 connectors are in good condition and tight
  7. 7Turn the batteries off and restart the equipment
  8. 8Redistribute the phases