STOP FAILURE
What This Code Means
Stop Failure alarm is activated; The control board shows STOP FAILURE alarm on the display; The LED of the STOP button lights up after a stop cycle is initiated; Engine running condition of 'started engine' is detected after a period of time during the stopping cycle; Control board displays 'ST op FaIlUrE' alarm; The LED of the STOP button lights up; Voltage values between genset phases (VG12, VG23, or VG31) are under minimum programmed limits; Frequency generated by the genset is under the minimum programmed frequency limits; No frequency signal detected on the first, second, or third phase; Unexpected engine shutdown; Engine fails to stop; Engine running condition of 'started engine' is detected after a stop command is initiated; Stop Failure alarm activated; Engine running condition detected during stop sequence; Voltage values between genset phases (VG12, VG23, or VG31) are under the minimum programmed limits; Genset frequency is under the minimum programmed frequency limits; No fr
Possible Causes
- •System continues to detect any engine running condition for 90 seconds after programmed stopping conditions are present
- •Engine continues running or is detected as running after the stopping cycle has completed (following the cooling time and PC output activation/deactivation)
- •Engine running condition of 'started engine' is detected after the designated stop cycle period has elapsed
- •Engine running condition is still detected for 90 seconds after programmed stopping conditions are present
- •Voltage values drop below limits defined in Thresholds table parameter 3 during the period defined by alarms table parameter 62
- •Genset frequency values are kept under the minimum programmed limits (Thresholds table parameter 6) during the stabilization time (alarms table parameter 65)
- •Controller does not detect all engine starting conditions (regulations table parameters 19 to 22) while the engine is running
- •Engine conditions (regulations table parameters 19 to 22) are not detected 15 seconds after a stop attempt
- •Engine running condition is still detected for 90 seconds after a stop command is initiated
- •Genset phase voltage drops below the thresholds defined in Thresholds table parameter 3
- •Genset frequency values remain below the thresholds defined in Thresholds table parameter 6 during the stabilization time programmed in Alarms table parameter 65
- •The controller does not detect all engine starting conditions (regulations table parameters 19 to 22) while the engine is running
- •All engine stop conditions (regulations table parameters 19 to 22) are not detected 15 seconds after an engine stop attempt
- •Engine fails to shut down after the stop cycle is initiated
Suggested Actions
- 1Configure alarm (alarms table parameter 63) to carry out stop with engine cooling
- 2Configure alarm (alarms table parameter 66) to carry out stop with engine cooling
- 3Disconnect the stop failure alarm (alarms table parameter 70) so the device will consider the engine stopped after waiting the maximum time of 15 seconds
- 4Ensure all stopping conditions are detected during the programmed time (alarms table parameter 71) to properly detect engine stop
- 5Stop engine with cooling (automatically triggered action configured by alarms table parameter 63)
- 6Stop engine with cooling (automatically triggered action configured by alarms table parameter 66)
- 7Disconnect the stop failure alarm (alarms table parameter 70) to allow the device to consider the engine stopped after waiting a maximum of 15 seconds
- 8Ensure all engine stopping conditions are detected during the programmed time (alarms table parameter 71)
Related Himoinsa Fault Codes
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for STOP FAILURE on your specific Himoinsa unit — cited to the OEM manual, not a forum guess.
TRY IT FREE