OVERLOAD ALARM

UnclassifiedElectrical

What This Code Means

Amperage values are kept over the maximum programmed overload limits during the stabilization time; Difference between any pair of real voltage values among generating set voltage phases (VG12, VG23, or VG31) is over the maximum asymmetry programmed limits; Overspeed alarm active; Immediate engine stop; Underspeed alarm active; Stop with engine cooling; Overload alarm active

Possible Causes

  • Amperage value is superior to the maximum programmed overload limit (Thresholds table parameter 7) but under the maximum limit of short-circuit (Thresholds table parameter 8) on the checked phases
  • Voltage difference between genset phases exceeds the maximum asymmetry programmed limits (Thresholds table parameter 4) during the stabilization time
  • Rotation speed of the engine ring gear exceeds the maximum limits (Thresholds table parameter 11) during the stabilization time (alarms table parameter 23)
  • Rotation speed of the engine ring gear is under the programmed minimum limits (Thresholds table parameter 12) during the stabilization time (alarms table parameter 26)
  • Effective amperage value in any phase is superior to the maximum programmed overload limit (Thresholds table parameter 7) but under the maximum limit of short-circuit (Thresholds table parameter 8)

Suggested Actions

  1. 1Stop with engine cooling