EMERGENCY STOP

UnclassifiedElectrical

What This Code Means

Engine stops immediately without cooling; Feeding to the power outputs of the measurement module (starting, pre-heating and engine stopping) is cut; Battery charge alternator failure alarm is triggered; Engine stop; Engine stop-inducing alarms; Warnings which do not stop the engines

Possible Causes

  • Emergency stop digital input (EMS) is detected
  • SETA input from the measurement module is triggered
  • Voltage value of the battery charge alternator voltage analog input (DI) does not exceed the voltage threshold of the started engine detection (Thresholds table parameter 21) during the configuration stabilization time
  • Emergency stop alarm activation
  • Low oil pressure alarm activation
  • High coolant temperature alarm activation
  • Thermal protection alarm activation
  • Programmable alarm activation
  • Poor quality of the mains signal

Suggested Actions

  1. 1Configure EMS digital input as normally open or normally closed (regulations table parameter 11)
  2. 2For engines programmed with stop by no-excitation, connect the SETA input to earth
  3. 3Configure the battery charge alternator alarm detection setting (alarms table parameter 10)
  4. 4Adjust the stabilization time associated with the battery charge alternator low alarm (Alarms table parameter 11)
  5. 5Verify or alter the battery charge alternator alarm active/inactive configuration (alarms table parameter 12)