INVERSE POWER
UnclassifiedElectrical
What This Code Means
Power obtained (mains or genset) is negative; Power exceeds the programmed factor of the nominal power; Power obtained (mains or genset) is negative and exceeds the programmed factor threshold; Genset frequency values obtained are kept over the maximum programmed limits; Erroneous order in the maximum voltage values of the genset (not phase 1, phase 2, and phase 3 in order); Power is out of the programmed limits
Possible Causes
- •Erroneous wiring of the current transformers
- •Genset frequency exceeds maximum programmed limits (Thresholds table parameter 5)
- •Device is configured to work with three-phase with neutral or three-phase without neutral and detects an incorrect phase sequence
Suggested Actions
- 1Correct the wiring of the current transformers
- 2Immediate engine stop
- 3Stop with engine cooling
Related Himoinsa Fault Codes
MAXIMUM GENSET FREQUENCYMAXIMUM GENSET FREQUENCY ALARMGENSET VOLTAGE ASYMMETRY ALARMMAXIMUM GENSET VOLTAGEERRONEOUS PHASE SEQUENCE OF THE GENSETMINIMUM GENSET FREQUENCYEMERGENCY STOPMINIMUM GENSET VOLTAGECEM7 LOW BATTERY VOLTAGE ALARMOVERLOAD ALARMBATTERY CHARGE ALTERNATOR FAILURE ALARMSHORT CIRCUIT