AUXILIARY SWITCH FAULT

UnclassifiedSensors

What This Code Means

Position-indicating contacts indicate ATS position changed when no transfer was called for; Both auxiliary switches are open or closed simultaneously; Controller unable to determine transfer switch position; Transfer switch in Normal position executes Engine Cooldown time delay and opens engine start contacts to stop generator set

Possible Causes

  • •Both auxiliary switches are open or closed
  • •Both auxiliary switches are open or closed so that the controller is unable to determine the transfer switch position
  • •Both auxiliary switches are open or closed so the controller is unable to determine transfer switch position
  • •Both auxiliary switches in the same state (both open or both closed)
  • •Controller cannot determine the transfer switch position
  • •Main shaft auxiliary switch error indicating multiple positions
  • •Main shaft auxiliary switches indicate that the ATS is in more than one position
  • •Position changed when no signal was sent to initiate the change
  • •Position-indicating contacts indicate ATS position changed when controller did not send a signal to transfer
  • •Position-indicating contacts indicate ATS position changed when no transfer was called for
  • •Position-indicating contacts indicate that the ATS position changed when no transfer was called for
  • •Transfer switch in intermediate position
  • •Uninitiated ATS position change
  • •Unsolicited ATS position change detected by position-indicating contacts

Suggested Actions

  1. 1Check the control contact operation
  2. 2Check the control contact operation.
  3. 3Check wiring and connections to position microswitches (see schematic drawing)
  4. 4Check wiring and connections to position microswitches.
  5. 5Check wiring and connections to position microswitches. See schematic drawing for connections
  6. 6Contact an authorized distributor/dealer for service if the fault persists
  7. 7Identify and correct the cause of the fault condition
  8. 8Inspect for signs of coil damage or overheating and replace coil if necessary
  9. 9Inspect for signs of coil damage or overheating and replace coil if necessary.
  10. 10Manually operate the transfer switch following safety precautions and instructions
  11. 11Manually operate the transfer switch, following safety precautions and instructions for your model
  12. 12Manually operate the transfer switch, following safety precautions and instructions for your model.
  13. 13Replace microswitch if necessary
  14. 14Replace microswitch if necessary.
  15. 15Reset the controller to clear the fault condition
  16. 16Reset the controller to clear the fault condition (press and hold the test and exercise pushbuttons simultaneously to clear fault and silence alarm)
  17. 17Reset the fault condition as described in Section 4.4.1
  18. 18Test position microswitch operation
  19. 19Test position microswitch operation.
  20. 20Test position microswitch operation. Replace microswitch if necessary