LOSSOFFIELD

UnclassifiedSensors

What This Code Means

Erratic power metering signal not consistent with system configuration; Reversing power direction does not resolve the problem; Automatic Paralleling Module (APM) has stopped communicating on RBUS; APM was detected on the RBUS network but is no longer communicating; Primary controller has lost communication with the secondary controller; A secondary controller was detected, then communication was lost; Generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds; Generator does not know if the metering is connected or the orientation of the connection; Generators cannot share load accurately until this information is known

Possible Causes

  • APM is unplugged
  • Bad wiring to the CT (Current Transformer)
  • Bus voltage on the other generator is not calibrated correctly
  • Bus voltage on this generator is not calibrated correctly
  • Generator voltage on other generator is not calibrated correctly
  • Generator voltage on this generator is not calibrated correctly
  • Intermittent RBUS connections
  • Intermittent connections on RBUS network wiring
  • Primary controller is powered down
  • RBUS disconnected
  • Secondary controller battery disconnected
  • System commissioning and startup not yet complete
  • Too much tension on wires from the CT to the controller
  • Updating firmware in secondary controller

Suggested Actions

  1. 1Check RBUS communication connections
  2. 2Check the battery connections
  3. 3Contact an authorized dealer for paralleling system troubleshooting and service
  4. 4See the APM instructions