METERINGOK

UnclassifiedSensors

What This Code Means

Erratic power metering signal not consistent with system configuration; Reversing power direction does not resolve the problem; Automatic Paralleling Module (APM) has stopped communicating on RBUS; APM was detected on the RBUS network but is no longer communicating; Primary controller has lost communication with the secondary controller; A secondary controller was detected, then communication was lost; Generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds; Generator does not know if the metering is connected or the orientation of the connection; Generators cannot share load accurately until this information is known

Possible Causes

  • APM is unplugged
  • Bad wiring to the CT (Current Transformer)
  • Bus voltage on the other generator is not calibrated correctly
  • Bus voltage on this generator is not calibrated correctly
  • Generator has verified that the metering is connected correctly and that the direction is consistent with expected power direction
  • Generator voltage on other generator is not calibrated correctly
  • Generator voltage on this generator is not calibrated correctly
  • Intermittent RBUS connections
  • Intermittent connections on RBUS network wiring
  • Primary controller is powered down
  • RBUS disconnected
  • Secondary controller battery disconnected
  • System commissioning and startup not yet complete
  • Too much tension on wires from the CT to the controller
  • Updating firmware in secondary controller

Suggested Actions

  1. 1Check RBUS communication connections
  2. 2Check the battery connections
  3. 3See the APM instructions