6279

UnclassifiedFuel

What This Code Means

Current consumption exceeds the DSE unit’s output specification; Fuel Relay Output not functioning for CAN ECU Power; CANbus communication interference or failure; CAN control non-functional; Current consumption exceeds DSE unit output specification; Fuel Relay Output failure; CANbus communication errors

Possible Causes

  • High current draw from engine starter solenoid
  • High current draw from fuel relay
  • Fuel Relay Output not configured correctly on applicable modules
  • Incorrect cable impedance
  • Improper screen/shield grounding
  • Deutz ECU parameter 4400 not enabled
  • Direct connection to high-draw component (Fuel Relay or Start Relay)
  • Incorrect module configuration
  • Unscreened cable
  • Incorrect screen grounding

Suggested Actions

  1. 1Use an external slave relay
  2. 2Check that current consumption does not exceed the DSE unit’s output specification
  3. 3Configure the Fuel Relay Output to CAN ECU Power
  4. 4Use only screened 120 Ω impedance cable approved specifically for use in CANbus applications
  5. 5Connect the CANbus screen at one end only
  6. 6Using the Deutz service tool software, change parameter 4400 on Page 6 to ‘1’
  7. 7Install an external slave relay
  8. 8Check current consumption against DSE unit output specification
  9. 9Use only screened 120 Ω impedance cable approved for CANbus applications
  10. 10Connect CANbus cable screen at one end only