ANALOGUE INPUT CONFIGURED AS DIGITAL

UnclassifiedLubrication

What This Code Means

Generator stops in a controlled manner; Module de-energises all 'Delayed Load Output' and 'Close Gen Output' outputs to remove the load from the generator; Module starts the Cooling timer and engine cools off-load before shutting down; Oil pressure is low with the engine at rest

Possible Causes

  • An auxiliary input configured to create a fault condition has become active
  • An analogue input configured to digital configured to create a fault condition has become active
  • The level detected by the fuel level sensor is below the low fuel level pre-set alarm setting
  • The level detected by the fuel level sensor is above the high fuel level pre-set alarm setting
  • Engine is at rest

Suggested Actions

  1. 1Rectify the alarm condition
  2. 2Accept and clear the alarm
  3. 3Press the Stop/Reset Mode button on the module to reset
  4. 4The module can be reset without rectifying the low oil pressure condition first (active from safety on exception)