2501

UnclassifiedElectrical

What This Code Means

Generator running underspeed for > 30 seconds when undervoltage alarm set; Single Zero Cross missing; Undervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general; One zero cross missing for greater than 1.5 seconds; Field Current measured value is above threshold; The controller fuse is missing or damaged in such a way that it does not work; Fuse problem must be detected for 1.5 seconds; Command and position feedback not matching or taking too much time to achieve; Governor in open position for greater than one second; Governor in closed position (commanded otherwise) for greater than one second; No message received for 1 second on CAN bus during startup; 12/24V Battery Type system mismatch; No response from I/O Extender 1 for 3 seconds; No response from I/O Extender 2 for 3 seconds; No response from I/O Extender 3 for 3 seconds; No response from I/O Extender 4 for 3 seconds; External Charger Fail digital input is True for 3 seconds while External Charge

Possible Causes

  • governor wire loose
  • governor module
  • fuel supply/control system
  • engine intake exhaust or mechanical issues
  • field boost hardware failure
  • overload
  • Missing / Damaged Fuse
  • faulty excitation winding
  • zero cross circuit
  • circuit in general
  • Firmware older than V1.30
  • Governor wire loose
  • Governor module
  • Problem with CAN bus interface
  • Dealer Config and the Digital Input for confirming a 12/24 V Battery Type system mismatch
  • Loss of communication with I/O Extender 1
  • Loss of communication with I/O Extender 2
  • Loss of communication with I/O Extender 3
  • Loss of communication with I/O Extender 4
  • External Charger Failure

Suggested Actions

  1. 1Test 68
  2. 2Procedure for Alarm E-Code 1905
  3. 3Procedure for Alarm E-Code 1916
  4. 4Remove Load
  5. 5Procedure for Alarm E-Code 2101
  6. 6Procedure for Alarm E-Code 2400
  7. 7Procedure for Alarm E-Code 2500
  8. 8Procedure for Alarm E-Code 2501
  9. 9Procedure for Alarm E-Code 2502
  10. 10Test 68 – Check Actuator and Mixer Function page 163
  11. 11Test 106 – Test CAN bus Communication page 174
  12. 12Confirm battery type settings
  13. 13Inspect RS-485 wiring/terminating jumper on I/O
  14. 14Confirm external charger settings on controller menu
  15. 15Check external battery charger
  16. 16Check Fuel Level