2101
What This Code Means
Generator produces low voltage at no-load; Generator shuts down for overload; Generator shuts down for over voltage; Generator running underspeed for > 30 seconds when undervoltage alarm set; Single Zero Cross missing; Undervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general; One zero cross missing for greater than 1.5 seconds; Field Current measured value is above threshold; The controller fuse is missing or damaged in such a way that it does not work; Fuse problem must be detected for 1.5 seconds; Command and position feedback not matching or taking too much time to achieve; Governor in open position for greater than one second; Governor in closed position (commanded otherwise) for greater than one second; Ground + Neutral Current is above threshold.; Generator Xfer Enabled Output has been mis-wired.; Incorrect DC AC wiring hook up.; Output current measured value is above threshold.; Field Current measured value is above threshold.; Current exceeds
Possible Causes
- •governor wire loose
- •governor module
- •Fuel supply problem
- •Shorted condition in a connected load
- •Shorted condition in one of the load circuits
- •Heavy capacitive load
- •fuel supply/control system
- •engine intake exhaust or mechanical issues
- •field boost hardware failure
- •overload
- •Missing / Damaged Fuse
- •faulty excitation winding
- •zero cross circuit
- •circuit in general
- •Firmware older than V1.30
- •Ground fault.
- •Mismatched wiring on Wire 194 and Wire 23.
- •Incorrect customer connection wiring.
- •Overload condition.
- •Over-current condition.
Suggested Actions
- 1Test 68
- 2Correct the fuel supply
- 3Open all load breakers and bring them on one at a time to determine which branch circuit is the cause of the problem.
- 4Procedure for Alarm E-Code 1905
- 5Procedure for Alarm E-Code 1916
- 6Remove Load
- 7Procedure for Alarm E-Code 2101
- 8Procedure for Alarm E-Code 2400
- 9Procedure for Alarm E-Code 2500
- 10Procedure for Alarm E-Code 2501
- 11Procedure for Alarm E-Code 2502
- 12Verify wiring on Wire 194 and Wire 23.
- 13Verify customer connection wiring.
- 14Test 28 – Test for an Overload Condition page 75
- 15Verify VCC settings.
- 16Contact Technical Support.
- 17Test 101 – Check for Short Circuits page 172
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for 2101 on your specific Generac unit — cited to the OEM manual, not a forum guess.
TRY IT FREE