1907

UnclassifiedElectrical

What This Code Means

Prolonged Undervoltage; Generator voltage below 80% of nominal for 10+ seconds.; Both Zero Crosses missing Undervoltage; Controller measuring no voltage resulting in undervoltage; Generator voltage less than 120V when undervoltage set; No field current during undervoltage alarm; Generator running underspeed for > 30 seconds when under - voltage alarm set; Single Zero Cross missing Undervoltage; After resuming from a load shed event, still undervoltage because of overload condition.; Generator Xfer Enabled Output has been mis - wired.; Incorrect DC AC wiring hook up.

Possible Causes

  • Brushless Alternator Problem 5 – Generator Shuts Down for Under Voltage page 57
  • Brushed Alternator Problem 1 – Generator Shuts Down for Under Voltage page 53
  • Faulty excitation winding
  • Zero cross circuit failure
  • Circuit in general failure
  • Loose wiring
  • Field boost hardware failure
  • Loose connections
  • Broken wire
  • Wire loose
  • Brush failure
  • Fuel supply/control system issues
  • Engine intake exhaust or mechanical issues
  • Overload condition
  • Miswiring

Suggested Actions

  1. 1Verify wiring on Wire 194 and Wire 23.