22

UnclassifiedCooling

What This Code Means

Controller senses a short circuit in starter solenoid circuit; Governor Actuator Overload; Governor actuator duration of operation at or near full-duty cycle is beyond the design limit; Low Oil Pressure Cutoff Switch fault; Temperature Sending Unit fault; Overprime; Actuator Overload; Faulty Oil Pressure Sender; Excessive Smoke Under Load; Faulty oil pressure sender indication

Possible Causes

  • Exhaust restriction
  • Loose or damaged connections at starter motor
  • Shorts and/or grounds at solenoid
  • Excessive load
  • Air intake restriction
  • Air leak in fuel system
  • Governor linkage binding
  • Incorrect high idle adjustment
  • Faulty injectors
  • Incorrect injection pump timing
  • Low compression
  • Faulty connections in wiring harness
  • Loss of switch continuity
  • Shorted wiring
  • Intake restriction
  • Exhaust back pressure
  • Open to ground
  • Poor brush condition and contact
  • Grounded or shorted sender lead
  • Low sender resistance

Suggested Actions

  1. 1Check injectors
  2. 2Check connections at starter motor
  3. 3Check shorts and/or grounds at solenoid
  4. 4Check load
  5. 5Check air intake restriction
  6. 6Check exhaust restriction
  7. 7Check air leak in fuel system
  8. 8Perform fuel flow test
  9. 9Check governor linkage for binding
  10. 10Check high idle adjustment
  11. 11Check injection pump timing
  12. 12Check compression
  13. 13Check connections in wiring harness
  14. 14Check switch continuity
  15. 15Check battery voltage
  16. 16Check fuel supply
  17. 17Check start/stop switch (local and remote)
  18. 18Check shorted wiring
  19. 19Check intake restriction
  20. 20Check governor actuator operation

Related Onan Fault Codes