45
UnclassifiedCooling
What This Code Means
Field Overload; Speed Sense Fault; Controller does not sense quadrature frequency and voltage; External Coolant Loss; Coolant in oil; Engine Unstable; Genset Hunts; Genset Surges; Speed sense loss; High exhaust temperature; Loss of Speed Sense; Excessive Fuel Pump Prime Time; Coolant Loss; Speed Sense Loss; High Exhaust Temp; Emergency Shutdown; Excessive Smoke Under Load
Possible Causes
- •AC output issues
- •Broken or loose switch leads
- •Control plugs not fully seated
- •Coolant in oil
- •Cracked or leaking hoses
- •Excessive load
- •Faulty generator brush block
- •Faulty generator rotor
- •Faulty generator stator assembly
- •Faulty genset control PCB
- •Faulty local or remote Start/Stop switches
- •Faulty pin connections
- •Faulty slip rings
- •Fuel lines leaking
- •Fuel supply issues
- •Grounded or shorted quad windings
- •Leaks or defects in radiator
- •Loose clamps
- •Loose hose clamps
- •Loose wiring connections
- •Low coolant level
- •Open circuit across pins P1-1 and P1-10 (field windings)
- •Open circuit across pins P1-3 and P1-9 (quadrature windings)
- •Open, short, or ground in rotor/stator windings
- •Opens, shorts, or grounds in field resistance
- •Opens, shorts, or grounds in quad resistance
- •Quad leads not fully seated in connector to control
- •Shorted wiring on set & remote
Suggested Actions
- 1Check F2 Fuse
- 2Check K2 relay and connections
- 3Check all pin connections and pin condition, and replace as necessary
- 4Check control
- 5Check control plugs fully seated
- 6Check field windings
- 7Check for leaking fuel lines
- 8Check for loose wiring connections
- 9Check fuel supply
- 10Check loads for proper operation
- 11Check quad leads fully seated in connector to control
- 12Check rotor/stator windings for opens/shorts/grounds
- 13Check starter circuits
- 14Disconnect genset control connector P1 and check for electrical continuity across pins P1-1 and P1-10 (field windings)
- 15Disconnect genset control connector P1 and check for electrical continuity across pins P1-3 and P1-9 (quadrature windings)
- 16Operate and check for leaks
- 17Pressure test coolant system
- 18Replace the generator stator assembly if the quadrature windings circuit is open
- 19Replace the genset control PCB
- 20Service or replace the generator rotor if the field windings circuit is still open
- 21Service the generator brush block and slip rings and repeat the test if the field windings circuit is open
- 22Verify proper field resistance reading, open to ground
- 23Visually check coolant level
- 24Visually check for coolant in oil
- 25Visually check for cracked or leaking hoses
- 26Visually check for leaks or defects in radiator
- 27Visually check for loose clamps