2100
UnclassifiedGeneral
What This Code Means
Ground + Neutral Current is above threshold.; Generator Xfer Enabled Output has been mis-wired.; Incorrect DC AC wiring hook up.; Output current measured value is above threshold.; Field Current measured value is above threshold.; Current exceeds 150% of rated current.; P-P or P-N short.; Gen output current above rated limit accumulates to 300% within 11 seconds.
Possible Causes
- •Ground fault.
- •I2T based detection.
- •Incorrect customer connection wiring.
- •Mismatched wiring on Wire 194 and Wire 23.
- •One of the two CTs is detecting an overload condition
- •Over-current condition.
- •Overload condition (Output Current Method)
- •Overload condition.
- •Overloaded - Default (Output Current Method)
- •Unit is overloaded
- •Unit is overloaded, one of the two CTs is detecting an overload condition
Suggested Actions
- 1Change load dynamics or utilize loadshed
- 2Check transfer switch loadshed functionality
- 3Contact Technical Support.
- 4Remove Load
- 5Test 101 – Check for Short Circuits page 172
- 6Test 28 – Test for an Overload Condition page 75
- 7Verify VCC settings.
- 8Verify customer connection wiring.
- 9Verify wiring on Wire 194 and Wire 23.