2100

UnclassifiedGeneral

What This Code Means

Ground + Neutral Current is above threshold.; Generator Xfer Enabled Output has been mis-wired.; Incorrect DC AC wiring hook up.; Output current measured value is above threshold.; Field Current measured value is above threshold.; Current exceeds 150% of rated current.; P-P or P-N short.; Gen output current above rated limit accumulates to 300% within 11 seconds.

Possible Causes

  • •Ground fault.
  • •I2T based detection.
  • •Incorrect customer connection wiring.
  • •Mismatched wiring on Wire 194 and Wire 23.
  • •One of the two CTs is detecting an overload condition
  • •Over-current condition.
  • •Overload condition (Output Current Method)
  • •Overload condition.
  • •Overloaded - Default (Output Current Method)
  • •Unit is overloaded
  • •Unit is overloaded, one of the two CTs is detecting an overload condition

Suggested Actions

  1. 1Change load dynamics or utilize loadshed
  2. 2Check transfer switch loadshed functionality
  3. 3Contact Technical Support.
  4. 4Remove Load
  5. 5Test 101 – Check for Short Circuits page 172
  6. 6Test 28 – Test for an Overload Condition page 75
  7. 7Verify VCC settings.
  8. 8Verify customer connection wiring.
  9. 9Verify wiring on Wire 194 and Wire 23.