1062
UnclassifiedGeneral
What This Code Means
Main controller detects no VSCF modbus messages have been received
Possible Causes
- •Comm's cable / connection has become faulty
- •Comm’s cable / connection has become faulty
- •Incorrectly shielded
- •Incorrectly shielded cable
- •One of the controllers is damaged
- •The AVR has no power to it
- •The firmware download has failed
- •Using a DMM on comms wires
- •Using a DMM on communication wires
Suggested Actions
- 1Check communication wires between controller and AVR for shorts, opens, proper routing, and check pin fit
- 2Check for correct firmware version
- 3Check shield wires are properly grounded
- 4Check static voltages on Communication wires with unit not running
- 5Check the LEDs on the AVR (green LED should be lit only)
- 6Check the LED’s on the AVR (green one should be lit only)
- 7Check the LED’s on the AVR (the green one should be lit only)