2112
UnclassifiedGeneral
What This Code Means
Ground + Neutral Current is above threshold.; Generator Xfer Enabled Output has been mis-wired.; Incorrect DC AC wiring hook up.; Output current measured value is above threshold.; Field Current measured value is above threshold.; Current exceeds 150% of rated current.; P-P or P-N short.; Gen output current above rated limit accumulates to 300% within 11 seconds.
Possible Causes
- •Ground fault.
- •Mismatched wiring on Wire 194 and Wire 23.
- •Incorrect customer connection wiring.
- •Overload condition.
- •Over-current condition.
- •I2T based detection.
Suggested Actions
- 1Verify wiring on Wire 194 and Wire 23.
- 2Verify customer connection wiring.
- 3Test 28 – Test for an Overload Condition page 75
- 4Verify VCC settings.
- 5Contact Technical Support.
- 6Test 101 – Check for Short Circuits page 172