1472

UnclassifiedSpeed

What This Code Means

Engine failed to crank after the generator control received a start signal; Generator set output current has exceeded the warning limit threshold for greater than the fixed time delay; Generator set output current has exceeded the shutdown limit threshold for greater than the fixed time delay; Engine RPM has decreased to zero while not in run at rated mode; Engine RPM has decreased to zero, while not in run at rated mode

Possible Causes

  • •Alternator output current (one or more phases) has exceeded the alternator's current rating
  • •Base board or harness connection fault
  • •Current level exceeds the instantaneous threshold
  • •Dead or weak battery
  • •Failed starter
  • •Generator set overload
  • •High AC Current condition active for longer than the set time delay
  • •Incorrect CTs, CT connections, or CT setup
  • •Incorrect calibration in the PowerCommand control
  • •Incorrect rating setup in control
  • •One or more phase currents exceeded high AC warning threshold for set time delay seconds
  • •Short or Overload
  • •Short or overload

Suggested Actions

  1. 1Attempt to start the generator and test for B+ at the starter supply lug
  2. 2Charge or replace the battery as necessary
  3. 3Check CTs and CT connections. Correct if necessary.
  4. 4Check continuity from P12 to the CTs (P12-1 to P12-4, P12-2 to P12-5, P12-3 to P12-6)
  5. 5Check for a short circuit to engine block ground
  6. 6Check if starter is defective if B+ is present at the starter supply lug
  7. 7Check load lead connections
  8. 8Check operation by disconnecting the load and restarting the generator set.
  9. 9Check the load
  10. 10Check the load and load cables. Repair if necessary.
  11. 11Check the rating setup in the control and correct if necessary
  12. 12Disconnect the AC harness from the load cables
  13. 13If B+ is present at the starter supply lug, the starter could be defective
  14. 14Inspect the AC harness and board connector pins
  15. 15Inspect the load cables and the AC harness connections
  16. 16Press the Reset/Fault acknowledge button on the display
  17. 17Reduce the generator set load by powering off unnecessary electrical loads
  18. 18Refer to Current Transformer Setup on page 3-4.
  19. 19Remove connector P12 from the Base board
  20. 20Repair harness/connector connections
  21. 21Verify battery voltage is at least 12 VDC (or 24 VDC if applicable)
  22. 22Visually inspect for corroded pins, bent or broken pins, pushed back or expanded pins